Latching Relay MMK

Brand :
OMRON

Caution

    Product Description

    A cost-effective industrial-use relay with a low power consumption.
    [Features]
    ·Type MM power relay with a mechanical lock latching system.
    ·Mechanically holds the operations.
    · Quick operation due to pulse transmitted electrical power.
    ·Wide operating temperature range from -10°C to +55°C.
    ·Models compliant with auxiliary power relays (JEC-174D) are also available.
    [Applications]
    ·Ideal for motor and control operation switching.

    Latching Relay MMK Series Specifications of OMRON Industrial Relays

    Number Of Poles Industrial Relays2 Poles (2 c)3 Poles (3 c)4 Poles (2 c + 2 a)
    FormatRated Voltage (V)FormatRated Voltage (V)FormatRated Voltage (V)
    Standard TypeModel MM2KPAC 100/(110), 200/(220)Model MM3KPDC 100/110Model MM4KPAC 100/(110), 200/(220)
    DC 24, 100/110DC 100/110
    DC Load Switching TypeModel MM2XKPDC 24, 100/110Model MM3XKPDC 100/110Model MM4XKPAC 100/(110)
    DC 24, 100/110, 125
    Standard Power Auxiliary Relay Type
    For DC Load Switching
    ----Model MM4XKP-JDDC 100/110
    Latching Relay MMK: related images

    MM2KP external appearance of Industrial Relays

    Latching Relay MMK: related images

    MM2(X)KP dimensional outline drawing of Industrial Relays

    • *Units: mm
    • *When the case-protection plate is attached to the MM2XKP, the width of the relay will be 55 mm max.
    Latching Relay MMK: related images

    Model MM2KP (standard type) terminal layout / internal schematics

    Latching Relay MMK: related images

    Model MM2XKP (DC load switching type) terminal layout / internal schematics

    Latching Relay MMK: related images

    MM4KP external appearance of Industrial Relays

    Latching Relay MMK: related images

    MM3(X)KP/MM4(X)KP dimensional outline drawing of Industrial Relays

    • *Units: mm
    • *When the case-protection plate is attached to the MM3, 4XKP, the width of the relay will be 73 mm max.
    Latching Relay MMK: related images

    Model MM3KP (standard type) terminal layout / internal schematics

    Latching Relay MMK: related images

    Model MM4KP (standard type) terminal layout / internal schematics

    Performance of OMRON Industrial Relays

    Contact Resistance *150 mΩ max.
    Set 2TimeAC: 30 ms max.
    DC: 60 ms max.
    Minimum Pulse WidthBoth AC and DC are 100 ms
    Reset *2Time30 ms max.
    Minimum Pulse WidthBoth AC and DC are 100 ms
    Maximum Switching FrequencyMechanical1,800 operations/hr
    Rated Load1,800 operations/hr
    Insulation Resistance *3100 MΩ min.
    Dielectric StrengthBetween Coil and Contacts2,000 V AC 50/60 Hz for 1 min
    Between Contacts of Different Polarity
    Between Set And Reset Coil
    Between Contacts of Same Polarity1,500 V AC 50/60 Hz for 1 min
    VibrationDurability10 to 55 to 10 Hz, 0.375-mm single amplitude (0.75-mm double amplitude)
    Malfunction10 to 35 to 10 Hz, 0.5-mm single amplitude (1-mm double amplitude)
    ShockDurability500 m/s2
    Malfunction50 m/s2
    DurabilityMechanical2,500,000 operations min. (at switching frequency of 1,800 operations/hr)
    Electrical *4500,000 operations min. (at 1,800 operations/hr under rated load)
    Failure Rate (P Level) (Reference Value *5)5 V DC 10 mA
    Ambient Operating Temperature-10 to +55°C (assuming no icing or condensation)
    Ambient Operating Humidity5 to 85% RH
    Weight· Standard type of Industrial Relays
    Model MM2KP approx. 375 g
    Model MM3KP approx. 550 g
    Model MM4KP approx. 570 g
    · DC load switching type
    Model MM2XKP approx. 380 g
    Model MM3XKP approx. 555 g
    Model MM4XKP approx. 580 g
    • The values given above are initial values of Industrial Relays.

    *1. Measurement conditions: 5 V DC, 1 A, voltage drop method.
    *2. Measurement conditions: Rated operating voltage applied, not including contact bounce. Ambient temperature: +23°C
    *3. Measured with a 500 V DC ohmmeter at the same places that the dielectric strength was checked.
    *4. Ambient temperature: +23°C
    *5. This value was measured at a switching frequency of 60 operations/min.

    • *See the catalog for dimensional drawings and ratings other than those detailed above.