(!)NOTE : Windows 7 users won’t be able to use some latest features of eCatalog/WOS since Microsoft is ending support for Windows 7 on 14 Jan, 2020. Please upgrade your system for uninterrupted services.
Select part number to Order Now/ Add to Cart
[Features]
· A series based on twin timer, star delta timer.
· UL, CSA, LR, NK, CCC acquired, EN61812-1 compatible safe design.
· Compatible with the CE mark.
· Because the time units enable separate ON time and OFF time setting, combinations of long term ON or OFF and short time ON or OFF are possible.
· Product line-up with the two types of operational mode of start flicker ON and start flicker OFF.
· Power sources for any low voltage (AC24 to 48/DC12 to 48V), any high voltage (AC100 to 240V/DC100 to 125V).
· 24 types of time ranges can be selected from among 0.05 seconds to 300 hours.
· Instantaneous output of 0 setting is possible.
· Because there is instantaneous output by revolving the scale in the direction of 0, the checking of the sequence operation and the like is simple.
· UL, CSA, NK, LR, CCR acquired, EN61812-1 compatible.
· Corresponds to the CE mark.
H3CR-F /-G / -H external appearance
Because the time units enable separate ON time and OFF time setting, combinations of long term ON or OFF and short time ON or OFF are possible.
Product range includes 2 types of operational modes: start flicker ON and start flicker OFF.
Power supplies for low voltage (24 to 48 V AC / 12 to 48 V DC) and high voltage (100 to 240 V AC / 100 to 125 V AC) can be freely selected.
24 types of time ranges can be selected, from 0.05 seconds to 300 hours.
Instantaneous output for zero set value is possible. There is instantaneous output by turning the scale in the 0 direction, making it easy to confirm sequence operations, etc.
Complies with UL, CSA, NK, LR, and CCC, and is EN61812-1 compliant. Conforms to the CE mark.
4 types of time ranges can be selected with a single device, from 0.5 seconds to 120 seconds.
Complies with UL, CSA, NK, and LR, and is EN61812-1 compliant. Conforms to CE mark, CCC*
*Series H3CR-G8L-30/-G8EL-31 are not compliant with safety standards.
4 types of time ranges can be selected for each series, from 0.05 seconds to 12 seconds for the S series and from 0.05 minutes to 12 minutes for the M series.
Complies with UL, CSA, NK, and LR, and is EN61812-1 compliant. Conforms to CE mark, CCC.
Variations In Operating Time | ±0.2% (percentage relative to maximum scale) or less (±0.2%, ±10 ms or less in the 1.2‑s, 3‑s range) | |
---|---|---|
Set Error | ±5% (percentage relative to maximum scale) ±50 ms or less | |
Recovery Time | 0.1 s Or Less | |
Voltage Effect | ±0.2% (percentage relative to maximum scale) or less (±0.2%, ±10 ms or less in the 1.2‑s, 3‑s range) | |
Temperature Effect | ±1% (percentage relative to maximum scale) or less (±1%, ±10 ms or less in the 1.2‑s, 3‑s range) | |
Insulation Resistance | 100 MΩ or more (at 500 V DC megger) | |
Withstand Voltage | 2,000 V AC, 50/60 Hz, 1 min (between charging metal part and non-charging metal part) 2,000 V AC, 50/60 Hz, 1 min (between control output and operation circuit) 2,000 V AC, 50/60 Hz, 1 min (between different pole contacts) 1,000 V AC, 50/60 Hz, 1 min (between discontinuous contacts) | |
Impulse Voltage | 5 kV (between power supply terminals); however, 1 kV for 24 to 48 V AC / 12 to 48 V DC types 5 kV (between conductive part terminal and exposed non-charging metal part) However, 1.5 kV for 24 to 48 V AC / 12 to 48 V DC types | |
Noise Resistance | Square-wave noise by noise simulator (pulse width 100 ns/1 μs rise 1 ns) ±1.5 kV (between power supply terminals) | |
Electrostatic Strength | 8 kV (Malfunction) 15 kV (Destruction) | |
Vibration | Endurance | 10 to 55 Hz, half amplitude 0.75 mm, 3 directions, 2 h each |
Malfunction | 10 to 55 Hz, half amplitude 0.5 mm, 3 directions, 10 min each | |
Shock | Endurance | 980 m/s2, 6 directions, 3 times each |
Malfunction | 98 m/s2, 6 directions, 3 times each | |
Life | Mechanical | 20 million operations or more (no load, switching frequency 1,800 operations/h) |
Electrical | 100,000 operations or more (250 V AC, 5 A, resistive load, switching frequency 1,800 operations/h)* | |
Protection Structure | IP40 (Panel Surface) | |
Mass | Approx. 100 g |
Series H3CR-F, H3CR-FN external shape
Series H3CR-F, H3CR-FN dimensional drawing
Part Number |
---|
H3CR-F8 AC24-48/DC12-48 |
H3CR-F8 AC100-240/DC100-125 |
H3CR-F8N AC24-48/DC12-48 |
H3CR-F8N AC100-240/DC100-125 |
H3CR-F AC24-48/DC12-48 |
H3CR-F AC100-240/DC100-125 |
H3CR-FN AC100-240/DC100-125 |
Part Number | Price | Minimum Order Qty. | Volume Discount | Days to Ship | Time specifications (s) | Power Supply Voltage | Dimension depth (mm) | Rated power supply voltage (V) |
---|---|---|---|---|---|---|---|---|
₹ 9,371.00 | 1 Piece(s) | 7 Day(s) or more | 0.05s to 300h | AC/DC | 52.3 | AC24 to 48/DC12 to 48 | ||
₹ 9,406.00 | 1 Piece(s) | 7 Day(s) or more | 0.05s to 300h | AC/DC | 52.3 | AC100 to 240/DC100 to 125 | ||
₹ 9,371.00 | 1 Piece(s) | 7 Day(s) or more | 0.05s to 300h | AC/DC | 52.3 | AC24 to 48/DC12 to 48 | ||
₹ 9,418.00 | 1 Piece(s) | 7 Day(s) or more | 0.05s to 300h | AC/DC | 52.3 | AC100 to 240/DC100 to 125 | ||
₹ 7,472.00 | 1 Piece(s) | Same day | 0.05s to 300h | AC/DC | 52.3 | AC24 to 48/DC12 to 48 | ||
₹ 9,419.00 | 1 Piece(s) | 7 Day(s) or more | 0.05s to 300h | AC/DC | 52.3 | AC100 to 240/DC100 to 125 | ||
₹ 9,377.00 | 1 Piece(s) | 5 Day(s) or more | 0.05s to 300h | AC/DC | 52.3 | AC100 to 240/DC100 to 125 |
Loading...
Display method | Analog | Mounting Method | Panel / surface mount (shared) | Output Method | Relay |
---|---|---|---|---|---|
Dimension vertical(mm) | 48 | Dimension width(mm) | 48 | Time ranges = N | 24 range |
Contact Configuration | 2c |
How can we improve?
How can we improve?
Thank you for your time.
Your feedback is essential for our continuous improvement
Privacy Policy
Thank you for your cooperation.
Thank you for your time.
Your feedback is essential for our continuous improvement
Please use the inquiry form.
Privacy Policy