(!)NOTE : Windows 7 users won’t be able to use some latest features of eCatalog/WOS since Microsoft is ending support for Windows 7 on 14 Jan, 2020. Please upgrade your system for uninterrupted services.
Select part number to Order Now/ Add to Cart
[Features]
· Ultra-small timer for use in sequence control incorporating a dedicated IC.
· High precision with a repeat error of ±1% (including first time value).
· Recover time including recovery during operation is less than 100ms.
· Easy time setting using the large dial in common with the +- driver.
· Semi-multi power source voltages.
· A standard product which acquired UL, CSA standards.
· EN61812-1 Compatible, corresponds to the CE mark.
External appearance of H3Y
Maximum scale time | Time Setting Range |
---|---|
0.5 s | 0.04 s to 0.5 s |
1s | 0.1 s to 1.0 s |
5 s | 0.2 s to 5.0 s |
10 s | 0.5s to 10 s |
30 s | 1.0 s to 30 s |
60 s | 2.0 s to 60 s |
120 s | 5.0 s to 120 s |
3 min | 0.1 min to 3 min |
5 min | 0.2 min to 5 min |
10 min | 0.5 min to 10 min |
30 min | 1.0 min to 30 min |
60 min | 2.0 min to 60 min |
3 h | 0.1 h to 3 h |
Model number | Series H3Y-2 (-0) | Series H3Y-4 (-0) | |
---|---|---|---|
Power supply voltage *6 | ・ 100 to 120 V AC, 50/60 Hz, 200 to 230 V AC, 50/60 Hz ・ 24 V AC, 50/60 Hz *1 ・DC12V ・DC24V ・DC48V ・DC100 to 110 V ・DC125V *2, *3 | ||
Allowable voltage fluctuation range | 85 to 110% of power supply voltage (However, 90 to 110% of power supply voltage only for 12 V DC specifications) *4 | ||
Power consumption | AC100 to 120 V | 1.5 VA (at 120 V AC) | |
AC200 to 230 V | 1.8 VA (at 230 V AC) | ||
AC24V | 1.5 VA (at 24 V AC) | ||
DC12V | 0.9 W (at 12 V DC) | ||
DC24V | 0.9 W (at 24 V DC) | ||
DC48V | 1.0 W (at 48 V DC) | ||
DC100 to 110 V | 1.3 W (at 110 V DC) | ||
DC125V | 1.3 W (at 125 V DC) | ||
Reset voltage | 10% or more of power supply voltage *5 | ||
Control output | 250 V AC 5 A, resistant load (cosø = 1) Minimum compatible load 5 V DC 1 mA (P level, reference value) Contact Materials: Ag | 250 V AC 3 A, resistant load (cosø = 1) Minimum compatible load 1 V DC 1 mA (P level, reference value) Contact Materials: Au clad + Ag alloy | |
Operating Ambient Temperature | -10 to +50℃ (However, do not freeze) | ||
Storage temperature | -25 to +65℃ (However, do not freeze) | ||
Operating ambient humidity | 35 to 85% |
*1. The inverter output should not be used as a power supply.
*2. Single-phase, full-wave-rectified power supplies can be used.
*3. Only the H3Y-2 and H3Y-2-0 types include 12 V DC models.
* 4. When using continuously at an operating ambient temperature of 50°C, 90 to 110% of the power supply voltage (95 to 110% for 12 V DC) should be used.
* 5. For reliable reset, 100 to 120 V AC should be set to 10 V AC, 200 to 230 V AC should be set to 20 V AC, and 100 to 110 V DC should be set to 10 V DC or less.
*6. A diode to prevent reverse voltages is provided only on models with a DC power supply voltage.
Model number | Series H3Y-2 (-0) | Series H3Y-4 (-0) | |
---|---|---|---|
Accuracy of operating time | ±1% or less (at maximum scale time) *1 | ||
Setting error | ±10% ±50 ms max. (at maximum scale time) | ||
Reset time | 0.1 s max. (including halfway reset) | ||
Influence of voltage | ±2% or less (at maximum scale time) *1 | ||
Influence of temperature | ±2% or less (at maximum scale time) *1 | ||
Insulation resistance | 100 MΩ or more (Measured at 500 V DC insulation resistance tester) | ||
Withstand voltage | 2,000 V AC, 50/60 Hz for 1 min (Between current-carrying terminals and exposed non-current-carrying metal parts, except for the terminal thread section) 2,000 V AC, 50/60 Hz for 1 min (Between operating power supply circuit and control output) 2,000 V AC, 50/60 Hz for 1 min (Between different pole contacts; 2-pole model) 1,500 V AC 50/60 Hz 1 min (Between different pole contacts; 4-pole model) 1,000 V AC 50/60 Hz 1 min (Between non-continuous contacts) | ||
Impulse voltage | Between power supply terminals: 3 kV, 1 kV for 12 V DC, 24 V DC, 48 V DC Between exposed non-current-carrying metal parts: 4.5 kV, 1.5 kV for 12 V DC, 24 V DC, 48 V DC | ||
Noise immunity | Square-wave noise by noise simulator (pulse width: 100 ns/1 μs, 1-ns rise) ±1.5 kV | ||
Static immunity | Malfunction: 4 kV, Destruction: 8 kV | ||
Vibration | Destruction | 10 to 55 Hz, 0.75-mm single amplitude for 1 h each in 3 directions | |
Malfunction | 10 to 55 Hz, 0.5-mm single amplitude for 10 min each in 3 directions | ||
Impact | Destruction | 1,000 m/s^2 for 3 times each in 6 directions *2 | |
Malfunction | 100 m/s^2 for 3 times each in 6 directions | ||
Lifespan | Mechanical | 10,000,000 operations min. (under no load at 1,800 operations/h) | |
Electrical | 2-pole: 500,000 operations min. (250 V AC 5 A, resistant load at 1,800 operations/h) (At normal temperature) 4-pole: 200,000 operations min. (250 V AC 3 A, resistant load at 1,800 operations/h) (At normal temperature) | ||
Protective structure | IP40 | ||
Weight | Approx. 50 g |
*1. ±10 ms is added to the above value for the 0.5 s range model.
*2. The destructive impact resistance test was performed on the timer.
Part Number |
---|
H3Y-2 AC24 30S |
Part Number | Price | Minimum Order Qty. | Volume Discount | Days to Ship | RoHS | Type | Time specifications (s) | Power Supply Voltage | Rated power supply voltage (V) | Contact Configuration | Terminal shape |
---|---|---|---|---|---|---|---|---|---|---|---|
₹ 2,170.00 | 1 Piece(s) | Available | Same day | - | Timer | 1.0s to 30s | AC-dedicated | AC24 | Time Limit 2c | Plug-in terminal |
Loading...
Display method | Analog | Output Method | Relay | Representative Standard | CE / UL / CCC / CSA |
---|---|---|---|---|---|
Dimension vertical(mm) | 52.6 | Dimension width(mm) | 28 | Dimension depth(mm) | 21.5 |
Time ranges = N | 1 range |
Please check the type/dimensions/specifications of the part H3Y-2 AC24 30S in the Solid State/Timer H3Y series.
Part Number |
---|
H3Y-2 AC100-120 120S |
H3Y-2 AC100-120 1S |
H3Y-2 AC100-120 30M |
H3Y-2 AC24 5S |
H3Y-2 AC24 60M |
H3Y-2 AC24 60S |
Part Number | Standard Unit Price | Minimum order quantity | Volume Discount | Days to Ship | RoHS | Type | Time specifications (s) | Power Supply Voltage | Rated power supply voltage (V) | Contact Configuration | Terminal shape |
---|---|---|---|---|---|---|---|---|---|---|---|
₹ 2,193.00 | 1 Piece(s) | Available |
Same day
Stock | - | Timer | 5.0s to 120s | AC-dedicated | AC100 to 120 | Time Limit 2c | Plug-in terminal | |
₹ 2,170.00 | 1 Piece(s) | Available |
Same day
Stock | - | Timer | 0.1s to 1.0s | AC-dedicated | AC100 to 120 | Time Limit 2c | Plug-in terminal | |
₹ 4,172.00 | 1 Piece(s) | 6 Day(s) or more | - | Timer | 1.0m to 30m | AC-dedicated | AC100 to 120 | Time Limit 2c | Plug-in terminal | ||
₹ 3,176.76 | 1 Piece(s) | 5 Day(s) | 10 | - | - | - | - | - | - | ||
₹ 3,824.15 | 1 Piece(s) | 5 Day(s) or more | - | - | 2.0 m to 60 m | Dedicated to DC | AC24 | Time Limit 2c | Plug-in terminal | ||
₹ 2,944.13 | 1 Piece(s) | 5 Day(s) | - | Timer | 2.0s to 60s | AC-dedicated | AC24 | Time Limit 2c | Plug-in terminal |
How can we improve?
How can we improve?
Thank you for your time.
Your feedback is essential for our continuous improvement
Privacy Policy
Thank you for your cooperation.
Thank you for your time.
Your feedback is essential for our continuous improvement
Please use the inquiry form.
Privacy Policy