Loading...

NAP Series Single-Phase Noise Filter (General-Purpose / Single-Stage Filter / External Pulse Voltage Attenuation)

Brand :
COSEL

Caution

    Product Description

    Push-down terminal block external pulse voltage attenuation (NAP)

    [Features]
    · External impulse high attenuation type.
    · Single phase 250V.
    · Quick and easy push-down terminal block adoption (patent and design registration pending).
    · With screw dropout prevention function

    INDEX

    Features of NAP series

    NAP series

    NAP series

    External impulse high attenuation type
    Single-phase 250 V
    It uses a quick and easy push-down terminal block (With screw fall prevention function)

    Ordering information

    Ordering information

    1 Series name
    2 Rated current
    3 Ground capacitor code

    • * The attenuation characteristic differs depending on the ground capacitor code.

    4 Option D: DIN rail mounting type

    • * The external shape differs when the option is set. Please refer to the drawing.

    Ground capacitor code

    CodeLeakage current
    Input 125/250 V 60 Hz
    Capacitor capacity
    (Nominal value)
    0005 µA / 10 µA maxN/A
    47150 µA / 100 µA max470 pF
    4720.5 mA / 1.0 mA max 4,700 pF

    Product specifications

    ItemNAP-04-472NAP-06-472NAP-10-472 NAP-16-472 NAP-20-472NAP-30-472
    Rated Voltage〔V〕AC 1⌀ 250 / DC250
    Rated current〔A〕4610162030
    Test voltage (Between terminals and mounting plates)2,500 V AC (cutoff current = 20 mA), 1-minute, normal temperature normal humidity
    Insulation resistance (Between terminals and mounting plates)500 V DC 100 MΩ min normal temperature normal humidity
    Leakage current 125/250 V 60 Hz0.5 mA / 1.0 mA max
    Voltage drop1.0 V max
    Safety standard certified temperature- 25 to + 85°C (Refer to the derating characteristics)
    Operating Temperature- 40 to + 85°C (Refer to the derating characteristics)
    Operating Humidity20 to 95% RH (No condensation)
    Storage temperature/humidity- 40 to + 85°C, 20 to 95% RH (No condensation)
    Vibration10 to 55 Hz, 19.6 m/s^2 (2 G), period 3 minutes X, Y, Z direction 1 hour each
    Impact196.1 m/s^2 (20 G) 11 ms X, Y, Z direction 1 time each
    Safety StandardUL1283, CSA C22.2 No.8 (C-UL), DIN EN60939 VDE0565 Teil 3-1, ENEC (Except for DC input)
    External dimensions (excluding protrusions) / weight53 × 41 × 92 mm (W × H × D) / 300 g max (Option: for -D, refer to the drawing)

    Circuit Configuration

    Circuit Configuration

    Derating characteristics

    Derating characteristics

    Drawing

    Since this product uses a push-down terminal block, it is shipped in the following conditions.
    1 Terminal block cover is stored.
    2 Terminal block screw is retained on the upper side.

    Standard type

    Standard type

    DIN rail mounting type

    DIN rail mounting type

    • * Tolerance: ±1
    • * Weight: 300 g max
    • * Mounting plate material: Steel (surface treatment: nickel plating) t = 1.0
    • * Case material: PBT
    • * Unit mm
    • * Terminal block tightening torque M4: 1.6 N⋅m (16.9 kgf⋅cm) max

    Precautions for mounting DIN rail

    Grounding through a DIN rail may not provide the proper noise attenuation effect.
    Grounding should be done by connecting to the protective ground terminal (PE) of the noise filter main body.
    There are 2 protective ground terminals, but you can use it even by connecting only one of them.

    Precautions for mounting DIN rail

    Characteristic data (Representative example)

    NAP-06-472

    Attenuation characteristic (Static characteristics)

    Attenuation characteristic (Static characteristics)

    Pulse attenuation characteristics pulse width 1 µs

    Pulse attenuation characteristics pulse width 1 µs

    NAP-10-472

    Attenuation characteristic (Static characteristics)

    Attenuation characteristic (Static characteristics)

    Pulse attenuation characteristics pulse width 1 µs

    Pulse attenuation characteristics pulse width 1 µs

    NAP-16-472

    Attenuation characteristic (Static characteristics)

    Attenuation characteristic (Static characteristics)

    Pulse attenuation characteristics pulse width 1 µs

    Pulse attenuation characteristics pulse width 1 µs

    NAP-20-472

    Attenuation characteristic (Static characteristics)

    Attenuation characteristic (Static characteristics)

    Pulse attenuation characteristics pulse width 1 µs

    Pulse attenuation characteristics pulse width 1 µs

    NAP-30-472

    Attenuation characteristic (Static characteristics)

    Attenuation characteristic (Static characteristics)

    Pulse attenuation characteristics pulse width 1 µs

    Pulse attenuation characteristics pulse width 1 µs

    NAP-06-472 | NAP Series Single-Phase Noise Filter (General-Purpose / Single-Stage Filter / External Pulse Voltage Attenuation) | COSEL | MISUMI India