NAP Series Single-Phase Noise Filter (General-Purpose / Single-Stage Filter / External Pulse Voltage Attenuation)

Caution
Product Description
Push-down terminal block external pulse voltage attenuation (NAP)
[Features]
· External impulse high attenuation type.
· Single phase 250V.
· Quick and easy push-down terminal block adoption (patent and design registration pending).
· With screw dropout prevention function
INDEX
Features of NAP series

NAP series
External impulse high attenuation type
Single-phase 250 V
It uses a quick and easy push-down terminal block (With screw fall prevention function)
Ordering information

1 Series name
2 Rated current
3 Ground capacitor code
- * The attenuation characteristic differs depending on the ground capacitor code.
4 Option D: DIN rail mounting type
- * The external shape differs when the option is set. Please refer to the drawing.
Ground capacitor code
| Code | Leakage current Input 125/250 V 60 Hz | Capacitor capacity (Nominal value) |
|---|---|---|
| 000 | 5 µA / 10 µA max | N/A |
| 471 | 50 µA / 100 µA max | 470 pF |
| 472 | 0.5 mA / 1.0 mA max | 4,700 pF |
Product specifications
| Item | NAP-04-472 | NAP-06-472 | NAP-10-472 | NAP-16-472 | NAP-20-472 | NAP-30-472 |
|---|---|---|---|---|---|---|
| Rated Voltage〔V〕 | AC 1⌀ 250 / DC250 | |||||
| Rated current〔A〕 | 4 | 6 | 10 | 16 | 20 | 30 |
| Test voltage (Between terminals and mounting plates) | 2,500 V AC (cutoff current = 20 mA), 1-minute, normal temperature normal humidity | |||||
| Insulation resistance (Between terminals and mounting plates) | 500 V DC 100 MΩ min normal temperature normal humidity | |||||
| Leakage current 125/250 V 60 Hz | 0.5 mA / 1.0 mA max | |||||
| Voltage drop | 1.0 V max | |||||
| Safety standard certified temperature | - 25 to + 85°C (Refer to the derating characteristics) | |||||
| Operating Temperature | - 40 to + 85°C (Refer to the derating characteristics) | |||||
| Operating Humidity | 20 to 95% RH (No condensation) | |||||
| Storage temperature/humidity | - 40 to + 85°C, 20 to 95% RH (No condensation) | |||||
| Vibration | 10 to 55 Hz, 19.6 m/s^2 (2 G), period 3 minutes X, Y, Z direction 1 hour each | |||||
| Impact | 196.1 m/s^2 (20 G) 11 ms X, Y, Z direction 1 time each | |||||
| Safety Standard | UL1283, CSA C22.2 No.8 (C-UL), DIN EN60939 VDE0565 Teil 3-1, ENEC (Except for DC input) | |||||
| External dimensions (excluding protrusions) / weight | 53 × 41 × 92 mm (W × H × D) / 300 g max (Option: for -D, refer to the drawing) | |||||
Circuit Configuration

Derating characteristics

Drawing
Since this product uses a push-down terminal block, it is shipped in the following conditions.
1 Terminal block cover is stored.
2 Terminal block screw is retained on the upper side.

Standard type

DIN rail mounting type
- * Tolerance: ±1
- * Weight: 300 g max
- * Mounting plate material: Steel (surface treatment: nickel plating) t = 1.0
- * Case material: PBT
- * Unit mm
- * Terminal block tightening torque M4: 1.6 N⋅m (16.9 kgf⋅cm) max
Precautions for mounting DIN rail
Grounding through a DIN rail may not provide the proper noise attenuation effect.
Grounding should be done by connecting to the protective ground terminal (PE) of the noise filter main body.
There are 2 protective ground terminals, but you can use it even by connecting only one of them.

Characteristic data (Representative example)
NAP-06-472

Attenuation characteristic (Static characteristics)

Pulse attenuation characteristics pulse width 1 µs
NAP-10-472

Attenuation characteristic (Static characteristics)

Pulse attenuation characteristics pulse width 1 µs
NAP-16-472

Attenuation characteristic (Static characteristics)

Pulse attenuation characteristics pulse width 1 µs
NAP-20-472

Attenuation characteristic (Static characteristics)

Pulse attenuation characteristics pulse width 1 µs
NAP-30-472

Attenuation characteristic (Static characteristics)

Pulse attenuation characteristics pulse width 1 µs