(!)NOTE : Windows 7 users won’t be able to use some latest features of eCatalog/WOS since Microsoft is ending support for Windows 7 on 14 Jan, 2020. Please upgrade your system for uninterrupted services.
Select part number to Order Now/ Add to Cart
A large white PV display realizes high visibility. Pursuing ease of use from selection to operation and setting. Added push-in Plus terminal block type to the 48 x 96 mm size lineup.
[Features]
·A white PV display with a height of 25 mm (E5AC) and 18 mm (E5EC/E5EC-B) has been adopted to improve visibility.
·Realization of high-speed sampling of 50 ms.
·For the 48 x 96 mm size, in addition to the screw terminal block, you can also select from the push-in Plus terminal block type that reduces wiring man-hours.
·Slim body with a depth of 60 mm (screw terminal block type).
·Easy connection with PLC by programless communication function. It is also possible to link between temperature controllers via component communication.
·A tool port is provided not only on the top of the main unit, but also on the front, and by connecting it to a computer using a communication conversion cable (sold separately), settings can be made without wiring the power supply. Easy setting from CX-Thermo (sold separately).
Temperature Controllers Model E5EC
Temperature Controllers Model E5EC-B
Temperature Controllers Model E5AC
Temperature Controllers Model E5AC-T
Power supply voltage | Power supply voltage Type A: AC100-240V 50/60Hz Power supply voltage Type D: AC24V 50/60Hz/DC24V | |
---|---|---|
Allowable voltage fluctuation range | 85 to 110% of power supply voltage | |
Power Consumption | Temperature Controllers Model E5EC/ Temperature Controllers Model E5EC-B | Option -000 type: 6.6VA or less (100-240V AC), 4.1VA or less (24V AC) / 2.3W or less (24V DC) Other than the above: 8.3VA or less (100-240V AC), 5.5VA or less (24V AC) / 3.2W or less (24V DC) |
Temperature Controllers Model E5AC | Option -000 type: 7.0VA or less (100-240V AC), 4.2VA or less (24V AC) / 2.4W or less (24V DC) Other than the above: 9.0VA or less (100-240V AC), 5.6VA or less (24V AC) / 3.4W or less (24V DC) | |
Sensor Input | Temperature Controllers input Thermocouple: K, J, T, E, L, U, N, R, S, B, C/W, PLII Platinum resistance thermometer: Pt100, JPt100 Non-contact temperature sensor (ES1B): 10 to 70°C, 60 to 120°C, 115 to 165°C, 140 to 260°C Analog input Current input: 4 to 20mA, 0 to 20mA Voltage input: 1 to 5V, 0 to 5V, 0 to 10V | |
Input impedance | Current input: 150 Ω or less, voltage input: 1 MΩ or more (When connecting to the ES2-HB-N/THB-N, use a 1:1 connection.) | |
Temperature Controllers Method | ON/OFF or 2-degree-of-freedom PID (with autotuning) | |
Temperature Controllers Output | Relay Output | 1a AC250V 5A (resistive load) Electrical life 100,000 times Minimum applicable load 5V 10mA (reference value) |
Voltage output (for driving SSR) | Output voltage: DC12V±20% (PNP) Maximum load current: 40mA, with short circuit protection circuit (Maximum load current: 21mA for models with control output 2) | |
Linear Current Output | DC4~20mA/DC0~20mA Load 500Ω or less Resolution Approx. 10,000 | |
Auxiliary Output | Score | 2 or 4 points (depending on model) |
Output Specifications | Relay output 1a AC250V, 2 output type: 3A (resistance load) or 4 output type: 2A (resistance load) Electrical life 100,000 times Minimum applicable load 5V 10mA (reference value) | |
Event Input | Score | 2, 4 and 6 points (depending on model) |
External contact input specifications | During contact input: ON: 1kΩ or less OFF: 100kΩ or more | |
Non-contact input: ON: Residual voltage 1.5V or less OFF: Leakage current 0.1mA or less | ||
Current flow: Approx. 7mA (per contact) | ||
Transmission Output | Score | 1 point (depending on the model: type with transmission output) |
Output Specifications | Current output: DC4-20mA Load: 500Ω or less Resolution: Approx. 10,000 Linear voltage output: DC1-5V Load: 1kΩ or more Resolution: Approx. 10,000 | |
Remote SP Input | Current input: 4 to 20 mA DC, 0 to 20 mA DC (input impedance 150 Ω or less) Voltage input: 1 to 5 V DC, 0 to 5 V DC, 0 to 10 V DC (input impedance 1 MΩ or more) | |
Potentiometer input* | 100Ω to 10kΩ | |
Setting method | Digital setting by front keys | |
Instruction method | 11-segment digital display and single-light-emitting display Character height: E5EC/E5EC-B: PV: 18.0 mm, SV: 11.0 mm, MV: 7.8 mm E5AC: PV: 25.0 mm, SV: 15.0 mm, MV: 9.5 mm 3-level display Contents: PV/SV/MV, PV/SV/Multi-SP or remaining soak time, etc. Number of digits: 4 digits for PV, SV, and MV | |
Multi-SP function | Up to eight target values (SP0 to SP7) can be stored and selected by event input, key operation, or serial communication | |
Bank switching function | none | |
Other features | Manual output, heating/cooling control, loop break alarm function, SP lamp, alarm function, heater break detection function (including SSR failure), 40% AT, 100% AT, operation amount limit, input digital filter, self-tuning, robust tuning, PV input correction, run/stop, protect, square root calculation function, operation amount change rate limit, simple calculation, temperature status display function, simple program function, input moving average, display brightness setting | |
Ambient temperature | -10 to +55°C (but no condensation or freezing) / 3-year warranty: -10 to +50°C (but no condensation or freezing) when installed as standard unit | |
Ambient humidity | Relative humidity 25-85% | |
Storage temperature | -25 to +65°C (but no condensation or freezing) | |
Altitude | Under 2,000m | |
Recommended fuse | T2A, AC250V Time lag low breaking capacity | |
Installation environment | Overvoltage Category II, Pollution Degree 2 (EN/IEC/UL 61010-1) |
*This function is not available on E5EC-B.
Power supply voltage | Power supply voltage Type A: AC100-240V 50/60Hz Power supply voltage Type D: AC24V 50/60Hz/DC24V | |
---|---|---|
Allowable voltage fluctuation range | 85 to 110% of power supply voltage | |
Power Consumption | 9.0VA or less (AC100-240V), 5.6VA or less (AC24V) / 3.4W or less (DC24V) | |
Sensor Input | Temperature Controllers input Thermocouple: K, J, T, E, L, U, N, R, S, B, C/W, PLII Platinum resistance thermometer: Pt100, JPt100 Non-contact temperature sensor (ES1B): 10 to 70°C, 60 to 120°C, 115 to 165°C, 140 to 260°C Analog input Current input: 4 to 20mA, 0 to 20mA Voltage input: 1 to 5V, 0 to 5V, 0 to 10V | |
Input impedance | Current input: 150 Ω or less, voltage input: 1 MΩ or more (When connecting to the ES2-HB-N/THB-N, use a 1:1 connection.) | |
Temperature Controllers Method | 2-degree-of-freedom PID (with autotuning) or ON/OFF | |
Temperature Controllers Output | Relay Output | 1a AC250V 5A (resistive load) Electrical life 100,000 times Minimum applicable load 5V 10mA (reference value) |
Voltage output (for driving SSR) | Output voltage: DC12V±20% (PNP) Maximum load current: 40mA, with short circuit protection circuit (Maximum load current: 21mA for models with control output 2) | |
Linear Current Output | DC4~20mA/DC0~20mA Load 500Ω or less Resolution Approx. 10,000 | |
Auxiliary Output | Score | 4 points |
Output Specifications | Relay output 1a AC250V, 4 output type: 2A (resistance load) Electrical life 100,000 times Minimum applicable load 5V 10mA (reference value) | |
Event Input | Score | 2, 4 and 6 points (depending on model) |
External contact input specifications | During contact input: ON: 1kΩ or less OFF: 100kΩ or more | |
Non-contact input: ON: Residual voltage 1.5V or less OFF: Leakage current 0.1mA or less | ||
Current flow: Approx. 7mA (per contact) | ||
Transmission Output | Score | 1 point (depending on the model: type with transmission output) |
Output Specifications | Current output: DC4-20mA Load: 500Ω or less Resolution: Approx. 10,000 Linear voltage output: DC1-5V Load: 1kΩ or more Resolution: Approx. 10,000 | |
Potentiometer Input | 100Ω to 10kΩ | |
Setting method | Digital setting by front keys | |
Instruction method | 11-segment digital display and single-light-emitting display character height PV: 25.0 mm, SV: 15.0 mm, MV: 9.5 mm 3-level display. Contents: PV/SP/program number, segment number, remaining time in segment, operation amount (valve opening) number of digits: 4 digits | |
Bank switching function | none | |
Other features | Manual output, heating/cooling control, loop break alarm function, SP lamp, alarm function, heater break detection function (including SSR failure), 40% AT, 100% AT, operation amount limit, input digital filter, robust tuning, PV input correction, protection, square root calculation function, operation amount change rate limit, simple calculation, temperature status display function, input moving average, display brightness setting | |
Ambient Temperature Controllers | -10 to +55°C (but no condensation or freezing) / 3-year warranty: -10 to +50°C (but no condensation or freezing) when installed as standard unit | |
Ambient humidity | Relative humidity 25-85% | |
Storage Temperature Controllers | -25 to +65°C (but no condensation or freezing) | |
Altitude | Under 2,000m | |
Recommended fuse | T2A, AC250V Time lag low breaking capacity | |
Installation environment | Overvoltage Category II, Pollution Degree 2 (EN/IEC/UL 61010-1) |
E5EC/E5EC-B/E5AC
E5AC-T
When the Temperature Controllers using the heating/cooling control function
(1) Temperature Controllers output allocation:
Auxiliary output is used as control output (cooling side).
(2) Temperature Controllers:
When performing PID control, heating side PID and cooling side PID can be set independently. This
also supports control systems with different response characteristics for the heating side and cooling side.
Part Number |
---|
E5AC-RX2ASM-010 |
Part Number | Price | Minimum Order Qty. | Volume Discount | Days to Ship | Output Type | Number of Control Points | Setting Method | Failure Detecting Function | Power Supply Voltage (V) | Control Output 1 | Control Output 2 | Auxiliary output points | Terminal shape | Event Input (Point) | Heater Breakage, SSR Fault Detection Capability | Specifications | Communication | Remote SP input | Transmission input | Transmission Output |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
₹ 32,389.47 | 1 Piece(s) | 21 Day(s) or more | Relay contact | 1 | Key input | Heater Breakage / SSR Breakdown | 100 to 240 VAC | Relay Output | No | 2 independent | Screw terminal Block Type | 4 | 1 | 96×96 mm | None | None | None | - |
Loading...
Input Method | Thermocouple / Platinum temperature measuring resistor / Non-Contact Temperature Sensor / Voltage / Current | Control Method | ON/OFF Control / PID control with auto tuning | Number of Input Points(pcs.) | 1 |
---|---|---|---|---|---|
Input type | Full multi-input |
Please check the type/dimensions/specifications of the part E5AC-RX2ASM-010 in the Temperature Controller (Digital Control Meter) [E5EC/AC] series.
Part Number |
---|
E5AC-CX2ASM-013 |
E5AC-CX4ASM-000 |
E5AC-PR4ASM-000 |
E5AC-RX2ASM-011 |
E5AC-RX2DSM-000 |
E5AC-RX4ASM-000 |
Part Number | Standard Unit Price | Minimum order quantity | Volume Discount | Days to Ship | Output Type | Number of Control Points | Setting Method | Failure Detecting Function | Power Supply Voltage (V) | Control Output 1 | Control Output 2 | Auxiliary output points | Terminal shape | Event Input (Point) | Heater Breakage, SSR Fault Detection Capability | Specifications | Communication | Remote SP input | Transmission input | Transmission Output |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
₹ 39,851.24 | 1 Piece(s) | 13 Day(s) or more | Current | 1 | Key input | No | 100 to 240 VAC | Linear Current Output | No | 2 independent | Screw terminal Block Type | 6 | None | 96×96 mm | None | Presence | Presence | - | ||
₹ 35,373.65 | 1 Piece(s) | 13 Day(s) or more | Current | 1 | Key input | No | 100 to 240 VAC | Linear Current Output | No | 4 (auxiliary outputs 1 and 2 with same common and auxiliary outputs 3 and 4 with same common) | Screw terminal Block Type | None | None | 96×96 mm | None | None | None | - | ||
₹ 37,613.11 | 1 Piece(s) | 13 Day(s) or more | Position Proportional | 2 | Key input | No | 100 to 240 VAC | Relay Output for Position Proportion | Relay Output for Position Proportion | 4 (auxiliary outputs 1 and 2 with same common and auxiliary outputs 3 and 4 with same common) | Screw terminal Block Type | None | None | - | None | None | - | None | ||
₹ 37,613.11 | 1 Piece(s) | 13 Day(s) or more | Relay contact | 1 | Key input | SSR Breakdown / Heater Breakage | 100 to 240 VAC | Relay Output | No | 2 independent | Screw terminal Block Type | 6 | 1 | 96×96 mm | None | Presence | Presence | - | ||
₹ 30,898.73 | 1 Piece(s) | 10 Day(s) or more | Relay contact | 1 | Key input | SSR Breakdown / No / Heater Breakage | 24 VAC/DC | Relay Output | No | 2 independent | Screw terminal Block Type | None | None | 96×96 mm | None | None | None | - | ||
₹ 31,644.78 | 1 Piece(s) | 6 Day(s) or more | Relay contact | 1 | Key input | SSR Breakdown / No / Heater Breakage | 100 to 240 VAC | Relay Output | No | 4 (auxiliary outputs 1 and 2 with same common and auxiliary outputs 3 and 4 with same common) | Screw terminal Block Type | None | None | 96×96 mm | None | None | None | - |
How can we improve?
How can we improve?
Thank you for your time.
Your feedback is essential for our continuous improvement
Privacy Policy
Thank you for your cooperation.
Thank you for your time.
Your feedback is essential for our continuous improvement
Please use the inquiry form.
Privacy Policy