Temperature controller (digital controller) E5CC

Caution
Product Description
Large white PV display realizes high visibility. Seeks ease of use from selection to operation and setting. Push-in Plus terminal block type lineup has been added.
[Features]
· White PV display of 15.2 mm height is adopted for improved visibility.
· Achieves high-speed sampling of 50 ms.
· In addition to the screw terminal block type, you can select from the push-in plus terminal block type that reduces wiring work and the plug-in type that allows the terminal block to be attached/detached.
· Slim body with depth of 60 mm (screw terminal block type).
· PLC and easy connection achieved by program-less communication function. Temperatures can be linked by component communication.
· Settings can be done by connecting to a PC using communication cable (sold separately), without power supply wiring. Easily configurable via CX-Thermo (sold separately).
Drawing
![Temperature controller (digital controller) [E5CC] E5CC external shape figure](http://in.misumi-ec.com/linked/vitem/mech/OMR1/221005345619/img/221005345619_01.jpg)
Model E5CC
![Temperature controller (digital controller) [E5CC] E5CC-B external shape figure](http://in.misumi-ec.com/linked/vitem/mech/OMR1/221005345619/img/221005345619_02.jpg)
Model E5CC-B
![Temperature controller (digital controller) [E5CC] E5CC-U external shape figure](http://in.misumi-ec.com/linked/vitem/mech/OMR1/221005345619/img/221005345619_03.jpg)
Model E5CC-U
![Temperature controller (digital controller) [E5CC] E5CC-T external shape figure](http://in.misumi-ec.com/linked/vitem/mech/OMR1/221005345619/img/221005345619_04.jpg)
Model E5CC-T
Product Specification
E5CC Rating
| Power supply voltage | Power supply voltage A type: 100 to 240 V AC 50/60 Hz Power supply voltage D type: 24 V AC 50/60 Hz / 24 V DC | |
|---|---|---|
| Allowable Voltage Fluctuation Range | 85 to 110% of power supply voltage | |
| Power consumption | Option -000 type: 5.2 VA max (100 to 240 V AC), 3.1 VA max (24 V AC) / 1.6 W max (24 V DC) Other than the above: 6.5 VA or less (AC 100 to 240 V), 4.1 VA or less (24 V AC) / 2.3 W or less (24 V DC) | |
| Sensor input | Temperature input Thermocouple: K, J, T, E, L, U, N, R, S, B, C/W, PLII Platinum Resistance Temperature Detector: Pt100, JPt100 Non-contact temperature sensor (Model ES1B): 10 to 70°C, 60 to 120°C, 115 to 165°C, 140 to 260°C Analog input Current input: 4 to 20 mA, 0 to 20 mA Voltage input: 1 to 5 V, 0 to 5 V, 0 to 10 V, 0 to 50 mV (0 to 50 mV is available only for model E5CC-U) | |
| Input impedance | Current input: 150 Ω or less, voltage input: 1 MΩ or more (When connecting model ES2-HB-N/THB-N, please use a 1:1 connection) | |
| Control method | ON/OFF or 2-degree-of-freedom PID (with auto-tuning) | |
| Control output | relay output | Model E5CC/E5CC-B: 1a 250 V AC 3 A (resistive load), electrical lifespan 100,000 operations, minimum applicable load 5 V 10 mA (reference value) Model E5CC-U: 1c 250 V AC 3 A (resistive load), electrical lifespan 100,000 operations, minimum applicable load 5 V 10 mA (reference value) |
| Voltage output (for SSR drive) | output voltage 12 V DC ±20% (PNP), maximum load current 21 mA, with short circuit protection circuit | |
| Linear current output | DC 4–20 mA/DC 0–20 mA, load 500 Ω or less, resolution approx. 10,000 | |
| Auxiliary output | Number of contacts | Model E5CC: 2 or 3 points (depending on model) Model E5CC-B: 2 points Model E5CC-U: 1 or 2 points (depending on model) |
| Output specifications | Relay output 1a 250 V AC, single output type: 3 A (resistive load), dual output type: Model E5CC/Model E5CC-U 3 A (resistive load), Model E5CC-B 2 A (resistive load), triple output type: 2 A (resistive load) Electrical lifespan: 100,000 operations; minimum applicable load: 5 V 10 mA (reference value) | |
| event input | Number of contacts | Model E5CC: 2 or 4 points (depending on model) Model E5CC-B: 2 points (depending on model) |
| External contact input specifications | When using contact input: ON: 1 kΩ or less, OFF: 100 kΩ or more | |
| For non-contact input: ON: residual voltage 1.5 V or less, OFF: leakage current 0.1 mA or less | ||
| Output current: approx. 7 mA (per contact) | ||
| transfer output | Number of contacts | 1 point (depending on model: with transfer output type) |
| Output specifications | Current output: DC 4–20 mA Load: 500 Ω or less Resolution: approx. 10,000 linear voltage output: DC 1–5 V Load: 1 kΩ or more Resolution: approx. 10,000 | |
| Setting Method | Digital setting with front keys | |
| Remote SP input | current input: DC 4–20 mA, DC 0–20 mA (input impedance: 150 Ω or less) voltage input: DC 1–5 V, DC 0–5 V, DC 0–10 V (input impedance: 1 MΩ or more) | |
| Display Type | 11-segment digital display and single-point light display Character height PV: 15.2 mm, SV: 7.1 mm | |
| Multi-SP function * | Stores up to 8 setpoints (SP0–SP7), selectable via event input, key operation, or serial communication | |
| Bank Switching function | Not Included | |
| Other functions | Manual output, heating/cooling control, loop break alarm function, SP lamp, alarm function, heater break detection function (including SSR failure), 40% AT, 100% AT, manipulated variable limit, input digital filter, self-tuning, robust tuning, PV input correction, run/stop, protection, square root calculation function, manipulated variable rate-of-change limit, simple calculation, temperature status display function, simple program function, input moving average, display brightness setting | |
| Operating ambient temperature | -10 to +55°C (no condensation or freezing) / With 3-year warranty: -10 to +50°C for standard standalone installation (no condensation or freezing) | |
| Operating Ambient Humidity | Relative humidity 25 to 85% | |
| Storage Temperature | -25 to +65°C (no condensation or freezing) | |
| High | 2,000 m or less | |
| Recommended fuse | T2A, 250 V AC time-lag low breaking capacity | |
| Installation environment | Overvoltage category II, Pollution degree 2 (EN/IEC/UL 61010-1) | |
*. When selecting from event input on model E5CC-B, the maximum number of setpoints is 4.
E5CC-T rating
| Power supply voltage | Power supply voltage A type: 100 to 240 V AC 50/60 Hz Power supply voltage D type: 24 V AC 50/60 Hz / 24 V DC | |
|---|---|---|
| Allowable Voltage Fluctuation Range | 85 to 110% of power supply voltage | |
| Power consumption | 7.5 VA or less (AC100 to 240 V), 4.1 VA or less (24 V AC) / 2.3 W or less (24 V DC) | |
| Sensor input | Temperature input Thermocouple: K, J, T, E, L, U, N, R, S, B, C/W, PLII Platinum Resistance Temperature Detector: Pt100, JPt100 Non-contact temperature sensor (Model ES1B): 10 to 70°C, 60 to 120°C, 115 to 165°C, 140 to 260°C Analog input Current input: 4 to 20 mA, 0 to 20 mA Voltage input: 1 to 5 V, 0 to 5 V, 0 to 10 V | |
| Input impedance | Current input: 150 Ω or less, voltage input: 1 MΩ or more (When connecting model ES2-HB-N/THB-N, please use a 1:1 connection) | |
| Control method | 2-degree-of-flexibility PID (with auto-tuning) or ON/OFF | |
| Control output | relay output | 1a 250 V AC 3 A (resistive load) Electrical lifespan: 100,000 operations Minimum applicable load: 5 V 10 mA (reference value) |
| Voltage output (for SSR drive) | output voltage 12 V DC ±20% (PNP), maximum load current 21 mA, with short circuit protection circuit | |
| Linear current output | DC 4–20 mA/DC 0–20 mA, load 500 Ω or less, resolution approx. 10,000 | |
| Auxiliary output | Number of contacts | 3 points |
| Output specifications | Relay output 1a 250 V AC, 3 output type: 2 A (resistive load) Electrical lifespan: 100,000 operations; minimum applicable load: 5 V 10 mA (reference value) | |
| event input | Number of contacts | 2 points or 4 points (depending on the model) |
| External contact input specifications | When using contact input: ON: 1 kΩ or less, OFF: 100 kΩ or more | |
| For non-contact input: ON: residual voltage 1.5 V or less, OFF: leakage current 0.1 mA or less | ||
| Output current: approx. 7 mA (per contact) | ||
| transfer output | Number of contacts | 1 point (depending on model: with transfer output type) |
| Output specifications | Current output: DC 4–20 mA Load: 500 Ω or less Resolution: approx. 10,000 linear voltage output: DC 1–5 V Load: 1 kΩ or more Resolution: approx. 10,000 | |
| Setting Method | Digital setting with front keys | |
| Display Type | 11-segment digital display and single-point light display Character height PV: 15.2 mm, SV: 7.1 mm | |
| Bank Switching function | Not Included | |
| Other functions | Manual output, heating/cooling control, loop break alarm function, SP lamp, alarm function, heater break detection function (including SSR failure), 40% AT, 100% AT, output limit, input digital filter, robust tuning, PV input correction, protection, square root calculation function, output rate-of-change limit, simple calculation, temperature status display function, input moving average, display brightness setting | |
| Operating ambient temperature | -10 to +55°C (no condensation or freezing) / With 3-year warranty: -10 to +50°C for standard standalone installation (no condensation or freezing) | |
| Operating Ambient Humidity | Relative humidity 25 to 85% | |
| Storage Temperature | -25 to +65°C (no condensation or freezing) | |
| High | 2,000 m or less | |
| Recommended fuse | T2A, 250 V AC time-lag low breaking capacity | |
| Installation environment | Overvoltage category II, Pollution degree 2 (EN/IEC/UL 61010-1) | |
Model number display
Screw terminal block type


*1. When the control output is a linear current output, options (81, 82, 83) with heater disconnection/SSR failure detection functions cannot be selected.
*2. When the auxiliary output is 0 (none), only option 80 (none) can be selected.
*3. The control output cannot be used as a transmission output.
- When using the heating/cooling control function
(1) Regarding the assignment of control outputs
If there is no control output 2: Use the auxiliary output as the control output (cooling side).
If there is a control output 2: Use the two control outputs for the heating side and cooling side, respectively.
(Either side can be used for heating or cooling.)
(2) About control
When using PID control, the heating side PID and cooling side PID can each be set independently.
Supports control systems with different response characteristics for the heating and cooling sides.
Push-in Plus Terminal Block Type


*1. If the control output is a linear current output, options (81, 82) with heater disconnection and SSR failure detection functions cannot be selected.
*2. The control output cannot be used as a transmission output.
About heating/cooling control
(1) About the assignment of control output
The auxiliary output is used as the control output (cooling side).
(2) About control
When using PID control, the heating side PID and cooling side PID can each be set independently.
Supports control systems with different response characteristics for the heating and cooling sides.
Plug-in type


*From production in May 2014, it can be used as a simple transmission output.
- When using the heating/cooling control function
(1) About the assignment of control output
The auxiliary output is used as the control output (cooling side).
(2) About control
When using PID control, the heating side PID and cooling side PID can each be set independently.
Supports control systems with different response characteristics for the heating and cooling sides.
Usage Examples
Name of each part

Main input/output functions

Technical Information
Input range
Temperature input

The compatible standards for each input type are as follows.
K, J, T, E, N, R, S, B: JIS C1602-2015, IEC 60584-1
L: Fe-CuNi, DIN 43710-1985
U: Cu-CuNi, DIN 43710-1985
C/W: W5Re/W26Re, JIS C1602-2015, ASTM E988-1990
JPt100: JIS C1604-1989, JIS C1606-1989
Pt100: JIS C1604-1997, IEC 60751
PLII: According to the PLATINEL II thermoelectric table by ENGELHARD
Analog input

*Only the E5CC-U model can be used (from units produced in May 2014 onward).
Compliant standards

*8. The E5CC-U model (plug-in type) is UL Listing certified only when used with Omron sockets (P2CF-11/P2CF-11-E).
(Please note that model P3GA-11 is not covered by UL Listing certification.)
*9. For supported models, please refer to the "Certification/Compliance" section on the manufacturer's website (www.fa.omron.co.jp/).