(!)NOTE : Windows 7 users won’t be able to use some latest features of eCatalog/WOS since Microsoft is ending support for Windows 7 on 14 Jan, 2020. Please upgrade your system for uninterrupted services.
Select part number to Order Now/ Add to Cart
[Features]
·Easy setting with DIP switch
·A 2-point alarm type has also been added to the series. Suitable for alarm applications
·Multi-input (thermocouple/platinum resistance thermometer) type is also available
·Easy-to-read digital display with character height of 13.5 mm
* The external dimensions are the same for both models with and without alarm.
No alarm type
Alarm type
Power supply voltage | AC100~240V 50/60Hz AC24V 50/60Hz/DC24V | |
---|---|---|
Allowable voltage fluctuation range | 85 to 110% of power supply voltage | |
Power Consumption | 5VA (AC100~240V) 3VA (AC24V)/2W (DC24V) | |
Temperature Controllers input | Thermocouple types: K, J, L Platinum resistance thermometer types: Pt100, JPt100 Thermistor type: E52-THE Thermocouple/Platinum resistance thermometer multi-input type : K, J, L, T, U, N, R, Pt100, JPt100 | |
Temperature Controllers Output | Relay Output | AC250V 3A (resistive load) 1c |
Voltage output (for driving SSR) | DC12V 21mA (with short circuit protection circuit) | |
Temperature Controllers Method | ON/OFF, 2-degree-of-freedom PID (with automatic PID parameter setting function) | |
Alarm Output | AC250V 1A (resistive load) 1a | |
Setting method | Digital setting by front keys | |
Instruction method | 7-segment digital display (character height 13.5 mm) and deviation indication | |
Other features | · Prohibits setting changes (key protect) · Input correction · Display unit switching (℃/°F) · Forward/reverse operation switching · Temperature Controllers range, sensor switching (K/J/L, Pt100/JPt100), thermocouple/platinum resistance thermometer multi-input type switches between thermocouple and platinum resistance thermometer · Control cycle switching · 8 mode alarm output · Sensor abnormality detection (excluding thermistor type) | |
Ambient Temperature Controllers | -10 to +55°C (but no freezing or condensation) / 3-year warranty: -10 to +50°C | |
Ambient humidity | Relative humidity 25-85% | |
Storage Temperature Controllers | -25 to +65°C (but no freezing or condensation) |
Note: Do not use the inverter output as a power supply.
Indication accuracy (ambient temperature 23℃) | Thermocouple: *1 (±1% of indicated value or ±2°C, whichever is greater) ±1 digit or less Platinum resistance thermometer: *2 (±0.5% of indicated value or ±1°C, whichever is greater) ±1 digit or less Thermistor: *3 (1%FS) ±1 digit or less | |
---|---|---|
Temperature Controllers effects | Thermocouple (R): (±2% PV or ±10°C, whichever is greater) ±1 digit or less Other thermocouple: (±2% PV or ±4°C, whichever is greater) ±1 digit or less Platinum resistance thermometer: (±1% PV or ±2°C, whichever is greater) ±1 digit or less Thermistor: (±2% FS) ±1 digit or less | |
Voltage Effects | ||
Effects of electromagnetic interference (according to EN61326-1) | ||
Adjustment sensitivity (at ON/OFF control) | 0.2%FS (0.1%FS for thermocouple/platinum resistance thermometer multi-input type) | |
Proportional Band | 1 to 999°C (self-tuning, automatically set by auto-tuning) | |
Integration Time | 1 to 1999s (automatically set by self-tuning and auto-tuning) | |
Differential Time | 1 to 1999s (automatically set by self-tuning and auto-tuning) | |
Alarm output setting range | Absolute value alarm: Same as control setting range Others: 0 to full scale input setting range [unit: °C or °F] Alarm hysteresis: 0.2 °C or °F (fixed) | |
Temperature Controllers Period | 2/20s | |
Sampling Period | 500ms | |
Insulation resistance | 20MΩ or more (at DC500V megger) | |
Withstand voltage | AC2,000V 50/60Hz 1min (between terminals of different polarity live parts) | |
Vibration resistance | malfunction | 10~55Hz 20m/s2 10min each in X, Y, and Z directions |
Durability | 10~55Hz 0.75mm 2h each in X, Y, and Z directions | |
Shock Resistant | malfunction | 100m/s26 directions 3 times each |
Durability | 300m/s26 directions 3 times each | |
lifespan | Electrical | Over 100,000 times (relay output type) |
mass | Approx. 110g (body only) | |
Protective structure | Front IP50, Enclosure Category 2 (according to IEC60529), Rear case IP20, Terminal IP00 | |
Memory Protection | Non-volatile memory (number of writes: 1 million times) | |
EMC | Radiated interference field strength EN55011 Group1 Class ANoise terminal voltage EN55011 Group1 Class AElectrostatic discharge immunity EN61000-4-2 : 4kV contact discharge (Level 2), 8kV air discharge (Level 3) Field strength immunity EN61000-4-3 : 10V/m (80 to 1,000MHz, 1.4 to 2.0GHz amplitude modulated)(Level 3), 10V/m (900MHz pulse modulated) Conducted interference immunity EN61000-4-6 : 3V (0.15 to 80MHz) (Level 2) First transient EN61000-4-4Burst noise immunity: 2kV power line (Level 3), 1kVinput/output signal line (Level 3) Surge immunity EN61000-4-5 : Power line normal mode 1kV common mode 2kV output line (relay output) normal mode 1kV common mode 2kV voltage dip/interruption immunity EN61000-4-11 :0.5 period, 100% (rated voltage) | |
Certification Standards | UL61010-1 (listing compatible) CSA C22.2 No.1010-1 | |
Compliance standards | EN61326-1, EN61010-1, IEC61010-1 |
Part Number |
---|
E5CS-R1PU-W AC100-240 |
Part Number | Price | Minimum Order Qty. | Volume Discount | Days to Ship | Input Method | Power Supply Voltage (V) | Control Output 1 | Alarm Output |
---|---|---|---|---|---|---|---|---|
₹ 16,519.36 | 1 Piece(s) | 5 Day(s) | Platinum temperature measuring resistor | 100 to 240 VAC | Relay | 1 alarm |
Loading...
Number of Input Points(pcs.) | 1 | Case color | Light Gray |
---|
Please check the type/dimensions/specifications of the part E5CS-R1PU-W AC100-240 in the Thermac S Electronic Temperature Controller [E5CS] series.
Part Number |
---|
E5CS-QGU-W AC100-240 |
E5CS-QKJU-W AC100-240 |
E5CS-QPU-W AC100-240 |
E5CS-R1TU-W AC100-240 |
E5CS-R2TU-W AC100-240 |
E5CS-RGDU-W AC/DC24 |
Part Number | Standard Unit Price | Minimum order quantity | Volume Discount | Days to Ship | Input Method | Power Supply Voltage (V) | Control Output 1 | Alarm Output |
---|---|---|---|---|---|---|---|---|
₹ 21,345.00 | 1 Piece(s) | 21 Day(s) or more | Thermistor | 100 to 240 VAC | Voltage output (for driving SSR) | No alarm | ||
₹ 20,159.00 | 1 Piece(s) | 5 Day(s) | Thermocouple | 100 to 240 VAC | Voltage output (for driving SSR) | No alarm | ||
₹ 15,072.12 | 1 Piece(s) | 21 Day(s) | Platinum temperature measuring resistor | 100 to 240 VAC | Voltage output (for driving SSR) | No alarm | ||
₹ 16,519.36 | 1 Piece(s) | 13 Day(s) | Platinum temperature measuring resistor / Thermocouple | 100 to 240 VAC | Relay | 1 alarm | ||
₹ 22,442.00 | 1 Piece(s) | 6 Day(s) | Platinum temperature measuring resistor / Thermocouple | 100 to 240 VAC | Relay | 2 alarms | ||
₹ 20,159.00 | 1 Piece(s) | 6 Day(s) | Thermistor | 24 VAC/DC | Relay | No alarm |