Thermac S Electronic Temperature Controller [E5CS]

Brand :
OMRON
Caution
Product Description
· Easily set with DIP switch
· Two alarm types ave been added to the series. Ideal for alarm applications
· Multi-input (thermocouple / platinum temperature-sensing resistance) types are also available
· Easy-to-read digital display with character height of 13.5 mm
Drawing
![Thermac S Electronic Temperature Controller [E5CS] External Shape Figure](http://content.misumi-ec.com/image/upload/t_msmwm_wyg/v1/p/jp/product/wysiwyg/221005345541/221005345541_001_20230801115855.jpg)
*The external dimensions are the same for both the type without alarm and the type with alarm.
Terminal arrangement
![Thermac S Electronic Temperature Controller [E5CS] External Shape Figure (No Alarm Type)](http://content.misumi-ec.com/image/upload/t_msmwm_wyg/v1/p/jp/product/wysiwyg/221005345541/221005345541_002_20230801115855.jpg)
Type without alarm
![Thermac S Electronic Temperature Controller [E5CS] External Shape Figure (With Alarm Type)](http://content.misumi-ec.com/image/upload/t_msmwm_wyg/v1/p/jp/product/wysiwyg/221005345541/221005345541_003_20230801115855.jpg)
Type with alarm
Product Specification
| Power supply voltage | 100 to 240 V AC 50/60 Hz 24 V AC 50/60 Hz / 24 V DC | |
|---|---|---|
| Allowable Voltage Fluctuation Range | 85 to 110% of power supply voltage | |
| Power consumption | 5 VA (100 to 240 V AC) 3 VA (24 V AC) / 2 W (24 V DC) | |
| Input | Thermocouple type: K, J, L Platinum resistance thermometer type: Pt100, JPt100 Thermistor type: Model E52-THE** Multi-input type for thermocouples and platinum resistance thermometers : K, J, L, T, U, N, R, Pt100, JPt100 | |
| Control output | relay output | 250 V AC 3 A (resistive load) 1c |
| Voltage output (for SSR drive) | 12 V DC 21 mA (with short circuit protection circuit) | |
| Control method | ON/OFF, 2 flexibility PID (with automatic PID parameter setting function) shared | |
| Alarm output | 250 V AC 1 A (resistive load) 1a | |
| Setting Method | Digital setting with front keys | |
| Display Type | 7-segment digital display (character height 13.5 mm) and deviation indication | |
| Other functions | · Setting change prohibition (key protect) · Input correction · Display unit switching (°C/°F) · Direct/reverse operation switching · Temperature range, sensor switching (K/J/L, Pt100/JPt100), For thermocouple/platinum resistance thermometer multi-input types, switching between thermocouple and platinum resistance thermometer · Control Cycle switching · 8-mode alarm output · Sensor abnormality detection (excluding thermistor type) | |
| Operating ambient temperature | -10 to +55°C (no freezing or condensation) / For 3-year warranty: -10 to +50°C | |
| Operating ambient humidity | Relative humidity 25 to 85% | |
| Storage temperature | -25 to +65°C (no freezing or condensation) | |
note. Do not use the output of an inverter as the power supply.
Performance
| Indication Accuracy (ambient temperature 23°C) | thermocouple: *1 (+/-1% of indicated value or +/-2°C, whichever is larger) +/- 1 digit or less platinum resistance thermometer: *2 (+/-0.5% of indicated value or +/-1°C, whichever is larger) +/- 1 digit or less Thermistor: *3 (1% FS) +/- 1 digit or less | |
|---|---|---|
| Effect of temperature | Thermocouple (R): (+/-2% PV or +/-10°C, whichever is greater) +/- 1 digit or less Other thermocouples: (+/-2% PV or +/-4°C, whichever is greater) +/- 1 digit or less Platinum resistance thermometer: (+/-1% PV or +/-2°C, whichever is greater) +/- 1 digit or less Thermistor: (+/-2%FS) +/-1 digit or less | |
| Effect of voltage | ||
| Effect of electromagnetic interference (according to EN61326-1) | ||
| Control sensitivity (When ON/OFF control) | 0.2%FS (For thermocouple/platinum resistance thermometer multi-input type: 0.1%FS) | |
| Proportional Band | 1 to 999°C (automatically set by self-tuning or auto-tuning) | |
| Integration Time | 1–1999 s (Automatically set by self-tuning or auto-tuning) | |
| Derivative Time | 1–1999 s (Automatically set by self-tuning or auto-tuning) | |
| Alarm Output Setting Range | Absolute value alarm: Same as control setting range Others: 0 to input setting range full scale [Unit: °C or°F] Alarm hysteresis: 0.2°C or°F (fixing) | |
| Control Cycle | 2/20 s | |
| Sampling period | 500 ms | |
| Insulation resistance | 20 MΩ or more (500 V DC insulation resistance tester) | |
| Withstand voltage | 2,000 V AC 50/60 Hz for 1 min (between terminals of different live parts) | |
| Vibration resistance | Malfunction | 10 to 55 Hz, 20 m/s2, 10 min in each direction of X, Y, and Z |
| Endurance | 10 to 55 Hz, 0.75 mm in each direction of X, Y, and Z for 2 hr | |
| Impact resistant | Malfunction | 100 m/s2 6 directions, 3 times each |
| Endurance | 300 m/s2 6 directions, 3 times each | |
| Lifespan | Electrical | Over 100,000 times (relay output type) |
| Weight | approx. 110 g (main body only) | |
| Protective Structure | Front: IP50, enclosure category 2 (according to IEC60529), rear case: IP20, terminal: IP00 | |
| Memory Protection | Non-volatile memory (write cycles: 1,000,000 times) | |
| EMC | Radiated emission field strength EN55011 Group 1 Class A Terminal noise voltage EN55011 Group 1 Class A ESD immunity EN61000-4-2 : 4 kV contact electric discharge (Level 2) 8 kV air electric discharge (Level 3) Electric field strength immunity EN61000-4-3 : 10 V/m (80–1,000 MHz, 1.4–2.0 GHz amplitude modulation) (Level 3) 10 V/m (900 MHz pulse modulation) Conducted Disturbance Immunity EN61000-4-6 : 3 V (0.15–80 MHz) (Level 2) Fast Transient EN61000-4-4 Burst Noise Immunity: 2 kV Power Line (Level 3) 1 kV Input/Output Signal Line (Level 3) Surge Immunity EN61000-4-5 : Power line Normal mode 1 kV Common mode 2 kV Output line (relay output) Normal mode 1 kV Common mode 2 kV Voltage dip/interruption immunity EN61000-4-11 : 0.5 cycle, 100% (rated voltage) | |
| Certification Standards | UL61010-1 (Listing supported) CSA C22.2 No.1010-1 | |
| Applicable standards | EN61326-1, EN61010-1, IEC61010-1 | |
·For U and L, within +/-2°C +/-1 digit.
·R of 200°C or less: +/-3°C +/-1 digit or less.
*2. In the case of platinum resistance temperature detectors, the following exceptions apply.
·For model E5CS-U, input setting value 1: 1%FS +/-1 digit or less.
*3. In the case of thermistors, the following exceptions apply.
·When using the°C unit setting, temperature indication ranges that exceed the set temperature range +/-10%FS are not covered by the accuracy guarantee.
·When using the°F unit setting, temperature indication ranges of 609 to 630°F for input setting numbers 4 and 9, as well as ranges that exceed -5%FS to +10%FS of the set temperature range, are not covered by the accuracy guarantee.