Loading...

Thermac S Electronic Temperature Controller [E5CS]

Brand :
OMRON

Caution

    Product Description

    · Easily set with DIP switch
    · Two alarm types ave been added to the series. Ideal for alarm applications
    · Multi-input (thermocouple / platinum temperature-sensing resistance) types are also available
    · Easy-to-read digital display with character height of 13.5 mm

    Drawing

    Thermac S Electronic Temperature Controller [E5CS] External Shape Figure

    *The external dimensions are the same for both the type without alarm and the type with alarm.

    Terminal arrangement

    Thermac S Electronic Temperature Controller [E5CS] External Shape Figure (No Alarm Type)

    Type without alarm

    Thermac S Electronic Temperature Controller [E5CS] External Shape Figure (With Alarm Type)

    Type with alarm

    Product Specification

    Power supply voltage100 to 240 V AC 50/60 Hz
    24 V AC 50/60 Hz / 24 V DC
    Allowable Voltage Fluctuation Range85 to 110% of power supply voltage
    Power consumption5 VA (100 to 240 V AC)
    3 VA (24 V AC) / 2 W (24 V DC)
    InputThermocouple type: K, J, L
    Platinum resistance thermometer type: Pt100, JPt100
    Thermistor type: Model E52-THE**
    Multi-input type for thermocouples and platinum resistance thermometers
    : K, J, L, T, U, N, R, Pt100, JPt100
    Control
    output
    relay output250 V AC 3 A (resistive load) 1c
    Voltage output
    (for SSR drive)
    12 V DC 21 mA (with short circuit protection circuit)
    Control methodON/OFF, 2 flexibility PID (with automatic PID parameter setting function) shared
    Alarm output250 V AC 1 A (resistive load) 1a
    Setting MethodDigital setting with front keys
    Display Type7-segment digital display (character height 13.5 mm) and deviation indication
    Other functions· Setting change prohibition (key protect)
    · Input correction
    · Display unit switching (°C/°F)
    · Direct/reverse operation switching
    · Temperature range, sensor switching (K/J/L, Pt100/JPt100),
      For thermocouple/platinum resistance thermometer multi-input types,
      switching between thermocouple and platinum resistance thermometer
    · Control Cycle switching
    · 8-mode alarm output
    · Sensor abnormality detection (excluding thermistor type)
    Operating ambient temperature-10 to +55°C (no freezing or condensation) / For 3-year warranty: -10 to +50°C
    Operating ambient humidityRelative humidity 25 to 85%
    Storage temperature-25 to +65°C (no freezing or condensation)

    note. Do not use the output of an inverter as the power supply.

    Performance

    Indication Accuracy
    (ambient temperature 23°C)
    thermocouple: *1
    (+/-1% of indicated value or +/-2°C, whichever is larger)
    +/- 1 digit or less
    platinum resistance thermometer: *2
    (+/-0.5% of indicated value or +/-1°C, whichever is larger)
    +/- 1 digit or less
    Thermistor: *3
    (1% FS) +/- 1 digit or less
    Effect of temperatureThermocouple (R):
    (+/-2% PV or +/-10°C, whichever is greater)
    +/- 1 digit or less
    Other thermocouples:
    (+/-2% PV or +/-4°C, whichever is greater)
    +/- 1 digit or less
    Platinum resistance thermometer:
    (+/-1% PV or +/-2°C, whichever is greater)
    +/- 1 digit or less
    Thermistor: (+/-2%FS) +/-1 digit or less
    Effect of voltage
    Effect of electromagnetic interference
    (according to EN61326-1)
    Control sensitivity
    (When ON/OFF control)
    0.2%FS
    (For thermocouple/platinum resistance thermometer multi-input type: 0.1%FS)
    Proportional Band1 to 999°C (automatically set by self-tuning or auto-tuning)
    Integration Time1–1999 s (Automatically set by self-tuning or auto-tuning)
    Derivative Time1–1999 s (Automatically set by self-tuning or auto-tuning)
    Alarm Output
    Setting Range
    Absolute value alarm: Same as control setting range
    Others: 0 to input setting range full scale [Unit: °C or°F] Alarm hysteresis: 0.2°C or°F (fixing)
    Control Cycle2/20 s
    Sampling period500 ms
    Insulation resistance20 MΩ or more (500 V DC insulation resistance tester)
    Withstand voltage2,000 V AC 50/60 Hz for 1 min (between terminals of different live parts)
    Vibration resistanceMalfunction10 to 55 Hz, 20 m/s2, 10 min in each direction of X, Y, and Z
    Endurance10 to 55 Hz, 0.75 mm in each direction of X, Y, and Z for 2 hr
    Impact resistantMalfunction100 m/s2 6 directions, 3 times each
    Endurance300 m/s2 6 directions, 3 times each
    LifespanElectricalOver 100,000 times (relay output type)
    Weightapprox. 110 g (main body only)
    Protective StructureFront: IP50, enclosure category 2 (according to IEC60529), rear case: IP20, terminal: IP00
    Memory ProtectionNon-volatile memory (write cycles: 1,000,000 times)
    EMCRadiated emission field strength EN55011 Group 1 Class A
    Terminal noise voltage EN55011 Group 1 Class A
    ESD immunity EN61000-4-2
    : 4 kV contact electric discharge (Level 2)
                                      8 kV air electric discharge (Level 3)
    Electric field strength immunity EN61000-4-3
    : 10 V/m (80–1,000 MHz, 1.4–2.0 GHz amplitude modulation) (Level 3)
    10 V/m (900 MHz pulse modulation)
    Conducted Disturbance Immunity EN61000-4-6
    : 3 V (0.15–80 MHz) (Level 2)
    Fast Transient EN61000-4-4
    Burst Noise Immunity: 2 kV Power Line (Level 3)
                                         1 kV Input/Output Signal Line (Level 3)
    Surge Immunity EN61000-4-5
    : Power line Normal mode 1 kV
    Common mode 2 kV
    Output line (relay output)
                                Normal mode 1 kV
    Common mode 2 kV
    Voltage dip/interruption immunity EN61000-4-11
    : 0.5 cycle, 100% (rated voltage)
    Certification StandardsUL61010-1 (Listing supported)
    CSA C22.2 No.1010-1
    Applicable standardsEN61326-1, EN61010-1, IEC61010-1
      *1. In the case of thermocouples, the following exceptions apply.
            ·For U and L, within +/-2°C +/-1 digit.
            ·R of 200°C or less: +/-3°C +/-1 digit or less.
      *2. In the case of platinum resistance temperature detectors, the following exceptions apply.
            ·For model E5CS-U, input setting value 1: 1%FS +/-1 digit or less.
      *3. In the case of thermistors, the following exceptions apply.
            ·When using the°C unit setting, temperature indication ranges that exceed the set temperature range +/-10%FS are not covered by the accuracy guarantee.
            ·When using the°F unit setting, temperature indication ranges of 609 to 630°F for input setting numbers 4 and 9, as well as ranges that exceed -5%FS to +10%FS of the set temperature range, are not covered by the accuracy guarantee.