Thermac NEO temperature controller (digital controller) [E5*N-H/E5*N-HT]

Caution
Product Description
Thermac NEO series, one of the best-selling temperature controller, from model selection to operation and maintenance.
A high-performance type that responds to higher-speed, higher-accuracy temperature and process control, and a program type that expands the range of compatible applications are also available.
Drawing
E5CN-H type
![Thermac NEO temperature controller (digital controller) [E5□N-H/E5□N-HT] E5CN-H type external shape figure](http://in.misumi-ec.com/linked/vitem/mech/OMR1/221005345529/img/221005345529_01.jpg)
note: Terminal unit cannot be removed.
Product Specification
Name of each part
E5CN-H type
![Thermac NEO temperature controller (digital controller) [E5□N-H/E5□N-HT] E5CN-H type parts identification figure](http://in.misumi-ec.com/linked/vitem/mech/OMR1/221005345529/img/221005345529_02.jpg)
Rating / Performance
E5CN-H type rating
| Power supply voltage | Type without D power supply voltage: AC100 to 240 V 50/60 Hz Type with D power supply voltage: 24 V AC 50/60 Hz / 24 V DC | |
|---|---|---|
| Allowable Voltage Fluctuation Range | 85 to 110% of power supply voltage | |
| Power consumption | When using AC100–240 V: 8.5 VA (Max.) (3.0 VA for model E5CN-HR2 at 100 V AC) When using AC/24 V DC: 5.5 VA (24 V AC) / 3.5 W (24 V DC) (Max.) (2.7 VA for model E5CN-HR2D at 24 V AC) | |
| Sensor input | Selectable from the following (fully multi input). Thermocouple: K, J, T, E, L, U, N, R, S, B, W, PLII Platinum resistance thermometer: Pt100, JPt100 Current input: 4 to 20 mA, 0 to 20 mA Voltage input: 1 to 5 V, 0 to 5 V, 0 to 10 V | |
| Input impedance | Current input: 150 Ω or less, voltage input: 1 MΩ or more (When connecting model ES2-HB-N, please use a 1:1 connection.) | |
| Control method | ON/OFF or 2-degree-of-freedom PID (with auto-tuning) | |
| Control output | relay output | 1a 250 V AC 3 A (resistive load) electrical lifespan: 100,000 cycles minimum applicable load: 5 V 10 mA |
| Voltage output (for SSR drive) | output voltage 12 V DC ±15% (PNP) Max. load current 21 mA, with short circuit protection circuit | |
| Current output | DC 4–20 mA/DC 0–20 mA load 600 Ω or less resolution approx. 10,000* | |
| Linear voltage output | DC 0–10 V (load 1 kΩ or more) Resolution: approx. 10,000 | |
| Auxiliary output | Number of contacts | Max. 2 contacts |
| Output specifications | Relay output 1a 250 V AC 3 A (resistive load) Electrical lifespan: 100,000 cycles Minimum applicable load: 5 V 10 mA | |
| Event input | Number of contacts | Max. 2 points (depending on model: only for types with event input B) |
| External contact input specifications | For contact input: ON: 1 kΩ or less OFF: 100 kΩ or more | |
| For non-contact input: ON: residual voltage 1.5 V or less OFF: leakage current 0.1 mA or less | ||
| Output current: approx. 7 mA (per contact) | ||
| Simple Calculation | Number of Calculation Formulas | Max. 8 (can be combined via internal auxiliary relays) |
| Calculation | · Logical operation: Any one of the following four patterns can be selected. Each contact can be inverted. (A and B) or (C and D), (A or C) and (B or D), A or B or C or D, A and B and C and D (A, B, C, and D are the four input points). · Delay: On-delay or off-delay can be applied to the above logic operation results. Setting time: 0–9999 seconds or 0–9999 minutes · Output inversion: Supported | |
| Output | 1 internal auxiliary relay per calculation formula | |
| Assignment of internal auxiliary relays | Up to 8 internal auxiliary relays (simple calculation results) can be assigned as follows: Event input operation, auxiliary output, or control output | |
| transfer output | Number of contacts | Maximum 1 point (depending on model: type with transfer output F) |
| Output specifications | Current output: DC 4–20 mA Load: 600 Ω or less Resolution: approx. 10,000 at 4–20 mA | |
| RSP input | Not Included | |
| Setting Method | Digital setting with front keys | |
| Display Type | 11-segment digital display and single-point light display (7-segment display also available) Character height PV: 11 mm, SV: 6.5 mm | |
| Bank Switching function | Included (Number of banks: 8) Local SP, alarm set values, PID group No. (PID constants, upper/lower limits for manipulated variable, etc.) | |
| Other functions | Manual output, heating/cooling control, loop break alarm function, SP lamp, alarm function, heater disconnection detection function (including SSR failure and heater overcurrent detection function), 40% AT, 100% AT, manipulated variable limit, input digital filter, self-tuning, temperature input correction, run/stop, protect, control output ON/OFF count function, square root calculation function, manipulated variable rate-of-change limit, PV/SV status display function, simple program function, automatic adjustment of cooling coefficient, etc. | |
| Operating ambient temperature | -10 to +55°C (no condensation or freezing) / For 3-year warranty: -10 to +50°C | |
| Operating Ambient Humidity | Relative humidity 25 to 85% | |
| Storage temperature | -25 to +65°C (no condensation or freezing) | |
*For current output type, control output 1 can also be used as a transmission output.
E5CN-H Type Performance
| Indication Accuracy | Thermocouple: (±0.1% of indicated value or ±1°C, whichever is greater) within ±1 digit*1 Platinum resistance thermometer: (±0.1% of indicated value or ±0.5°C, whichever is greater) within ±1 digit analog input: +/-0.1%FS +/-1 digit or less CT input: +/-5%FS +/-1 digit or less | ||
|---|---|---|---|
| Transmission output accuracy | Within +/-0.3%FS | ||
| Effect by Temperature*2 | Thermocouple input (R, S, B, W, PLII): (the greater of +/-1%PV or +/-10°C) +/-1 digit or less Other thermocouple input: (the greater of +/-1%PV or +/-4°C) +/-1 digit or less*3 Platinum resistance thermometer input: (the greater of +/-1%PV or +/-2°C) +/-1 digit or less analog input: (±1%FS) ±1 digit or less | ||
| Effect of voltage*2 | |||
| Effect of electromagnetic interference (according to EN61326-1) | |||
| Input sampling period | 60 ms | ||
| Control sensitivity | Temperature input: 0.1 to 3240.0°C or°F (in 0.1°C or°F increments) analog input: 0.01 to 99.99%FS (0.01%FS increments) | ||
| Proportional Band (P) | Temperature input: 0.1 to 3240.0°C or°F (in 0.1°C or°F increments) analog input: 0.1 to 999.9%FS (0.1%FS increments) | ||
| Integration Time (I) | 0.0 to 3240.0 s (0.1 s unit) | ||
| Derivative Time (D) | 0.0 to 3240.0 s (0.1 s unit) | ||
| Control Cycle | 0.5, 1 to 99 s (1 s increments) | ||
| Manual reset value | 0.0 to 100.0% (0.1% increments) | ||
| Alarm setting range | -19999 to 32400 (Decimal point position depends on input type) | ||
| Effect of signal source resistance | Thermocouple: 0.1°C/Ω or less (100 Ω or less), Platinum resistance thermometer: 0.1°C/Ω or less (10 Ω or less) | ||
| Insulation resistance | 20 MΩ or more (500 V DC insulation resistance tester) | ||
| Withstand voltage | 2,300 V AC 50 or 60 Hz 1 min (different-pole live parts terminals) | ||
| Vibration | Malfunction | 10 to 55 Hz, 20 m/s2, 10 min in 3-axis directions | |
| Endurance | 10 to 55 Hz, 0.75 mm single amplitude, 2 hr in 3-axis directions | ||
| Impact | Malfunction | 100 m/s2, 3-axis directions, 3 times each | |
| Endurance | 300 m/s2, 3-axis directions, 3 times each | ||
| Weight | main body: approx. 150 g installation: approx. 10 g | ||
| Protective Structure | Front: IP66, rear case: IP20, terminal: IP00 | ||
| Memory Protection | Non-volatile memory (write cycles: 1,000,000 times) | ||
| Setting Tool | CX-Thermo Ver.4.0 or higher | ||
| Port for Setting Tool | Bottom surface of E5CN-H: Connect between the PC-side USB port and the bottom surface port of E5CN-H using the USB-serial conversion cable E58-CIFQ1. *4 | ||
| Standard | Certification Standards | UL61010-1, CSA C22.2 No.1010-1 | |
| Applicable standards | EN61010-1 (IEC61010-1): Pollution degree 2, overvoltage category II, Lloyd's standard*5 | ||
| EMC Directive | EMI EN61326-1 *6 Radiated disturbance electric field strength EN55011 Group 1 class A Terminal noise voltage EN55011 Group 1 class A EMS EN61326-1 *6 Electrostatic Discharge Immunity EN61000-4-2 Electromagnetic Field Strength Immunity EN61000-4-3 Burst Noise Immunity EN61000-4-4 Conducted Disturbance Immunity EN61000-4-6 Surge immunity EN61000-4-5 Power supply frequency magnetic field immunity EN61000-4-8 Voltage dip/interruption immunity EN61000-4-11 | ||
*1. ±2°C ±1 digit or less for K (-200 to 1300°C range), T, N at -100°C or less, and U, L. No regulations for B of 400°C or less. ±3°C or less for B of 400 to 800°C.
+/-3°C +/-1 digit or less for R and S of 200°C or less. W: (+/-0.3% of PV or +/-3°C, whichever is larger) +/-1 digit or less.
PLII: (+/-0.3% of PV or +/-2°C, whichever is larger) +/-1 digit or less.
*2. Conditions: Ambient temperature: -10°C to 23°C to 55°C Voltage range: -15% to +10% of rated voltage
*3. For K sensors, below -100°C: within ±10°C
*4. Simultaneous use of external serial communication (RS-232C or RS-485) and configuration tool cable communication is possible
*5. For compliance with Lloyd's standards, please refer to page 144 of the digital catalog, "Compliance with Marine Standards."