Cable NA400 250 V 400 °C Heat-Resistant

Cable NA400 250 V 400 °C Heat-Resistant

Move the mouse over or click the image to zoom

  • Heat-Resistant
  • Strand Wire
You can add up to 6 items per a category to the compare list.

Part Number :
  • Order Qty :
  • Price :
    ---
  • Total Price :
    ---
  • Days to ship :
    ---

Select part number to Order Now/ Add to Cart


● It uses a nickel wire conductor offering excellent heat and corrosion resistance with multiple layers of glass-mica-polyimide composite tape over the conductor, silica fiberglass braiding, and polyimide baked paint insulation.
● Non-asbestos heat resistant wires.
● Conductor uses JIS2532 (general use resistance wire) compatible nickel wire strand.

· Be careful not to confuse total length and quantity when ordering.
∙ Please pay attention to humidity for usage under low temperature.


* Color and softness may vary slightly due to manufacturer changes.

Electrical Appliance and Material Safety Law certificate has not been obtained.

PDF

My Components
My Components
Similar ProductsSimilar Products
Product DetailProduct Detail

Product Description

Super heat-resistant single core wire for low-current circuits. It is braided with silica glass fiber and coated with polyimide paint and baked to form an insulator.

Specifications

NA400 250 V 400 °C Heat-Resistant:Related Image

Model NumberSection Area
(mm²)
NA4000.75 * (AWG18)
1.25 * (AWG16)
2 * (AWG14)
3.5 * (AWG12)
5.5 * (AWG10)
* AWG size (AWG ~ ) is to be used only as a guide. Refer to the comparison table on >>Click here for details.


Be sure to read the following precautions when you place an order.
* Length in "m" is included in our model numbers. Always specify quantity as number of units, not as meters.
* For the latest information regarding standard unit price, quantity slide unit price, shipment days, etc., refer to the Misumi VONA e-catalog.

More Information

Operating Temperature Range0 ~ 400°C
Bending RadiusFinished Outer Diameter x 25 (Fixed Part Only)

Model NumberSection Area
(mm²)
ColorTotal Length
(m)
ConductorComposite Tape Thickness (mm)Braid Thickness (mm)Finished Outer Diameter (mm)Electrical PropertiesApproximate Mass
kg / km
Configuration
(Cable / mm)
Outside Diameter
(mm)
Conductor Resistance
Ω / km (20°C)
Insulation Resistance
MΩ / km (20°C)
Test Voltage
V / Min
Allowable Current
A (30 °C)
NA4000.75 * (AWG18)(Brown)1 ~ 100
(Specify
1 m Increment)
30/0.181.10.250.62.8126.81015001225.0
1.25 * (AWG16)50/0.181.50.73.4761830.0
2 * (AWG14)37/0.261.83.749.32535.0
3.5 * (AWG12)66/0.262.44.327.73546.0
5.5 * (AWG10)35/0.453.10.85.217.64275.0
* AWG size (AWG ~ ) is to be used only as a guide. Refer to the comparison table on >>Click here for details. * Allowable current is to be used only as a reference value and is not guaranteed.
* For the outer diameter size of cables, wire sheath (coat), etc., refer to "Finished Outer Diameter" in the table above.

NA400 250 V 400 °C Heat-Resistant:Related Image

Current Reduction Factor
Ambient Temperature (°C)30 or less405060708090100
Current Reduction Factor1.000.990.980.970.960.950.940.93
 
110120130140150160170180190200
0.920.910.900.890.870.860.850.840.820.80
 
210220230240250260270280290300
0.790.770.750.730.720.700.670.660.630.60
 
310320330340350360370380390400
0.580.550.510.480.440.400.340.280.200.00
Allowable current value indicates the calculated value of 1 cable laid aboveground in ambient temperature of 30°C, and is not a guaranteed value.
If the ambient temperature is 30 °C or above, the above current reduction factor is multiplied by the allowable current.
(Example) Allowable current value 12 x 0.99 = 11.88 (A) when the ambient temperature for 0.75 mm2 is 40 °C
Part Number
NA400-1.25-[1-99/1]
NA400-2-[1-99/1]
NA400-3.5-[1-99/1]
NA400-5.5-[1-99/1]
Part NumberPriceMinimum Order Qty.Volume DiscountDays to ShipOverall Length
(m)

-

1 Piece(s) 6 Day(s) or more 1 ~ 99

-

1 Piece(s) 6 Day(s) or more 1 ~ 99

-

1 Piece(s) 6 Day(s) or more 1 ~ 99

-

1 Piece(s) Quote 1 ~ 99
Part Number
Part NumberPriceMinimum Order Qty.Volume DiscountDays to ShipOverall Length
(m)

Loading...

  1. 1
  • Not a MISUMI customer yet?
  • Register and enjoy 20% Off
  • on your 1st order! *
  • Download CAD data and product data for more than 12 Mio. products.
  • Configure your drawing parts in the MISUMI Online Shop and save time and resources.
  • Reduce your process costs with the MISUMI Online Shop.
X
whatsapp-qr whatsapp-icon
Close

Comparison list

Please select a default language