(!)NOTE : Windows 7 users won’t be able to use some latest features of eCatalog/WOS since Microsoft is ending support for Windows 7 on 14 Jan, 2020. Please upgrade your system for uninterrupted services.
Select part number to Order Now/ Add to Cart
Temperature Controllers Standard Type
Temperature controllers are devices used to adjust the temperature of the controlled device to the set target temperature
[Feature]
● Input : Thermocouple (K, J, R, T, N, S, B) and Resistance thermometer (Pt100Ω / JPt100Ω.)
● Output : Relay contact output or SSR drive output free switching
● Power Supply Voltage : AC100~240VAC~50/60Hz±10%
● Mounting Size L X H (mm.) : 45 X 45
[Application]
It is used to adjust the temperature of the controlled device to the set target temperature
- Features both relay contact output and SSR drive output, allowing for easy switching between output types to suit different applications and reducing the need for multiple devices.
- Operates on a wide range of voltage and frequency, within specified ranges.
- High Accuracy: Features a specific internal operation accuracy.
- Mounting Size: With dimensions of 45 x 45 mm, the compact design allows for easy installation in tight spaces.
- Operating Environment: Suitable for use in environments with temperatures ranging from -10‹C to +60‹C and humidity levels of 0-90RH%.
MISUMI Standard
Cheaper Price
Product Variety
3D CAD Support
Part Number |
---|
C-MTCTRS |
Part Number | Price | Minimum Order Qty. | Volume Discount | Days to Ship |
---|---|---|---|---|
₹ 2,988.00 | 1 Piece(s) | Available | Same day |
Loading...
Item | C-MTCTRS (Standard Type) | C-MTCTRST (RS485 Communication Type) |
Panel Dimension | 48×48 | 48×96 |
Control Output | Relay contact output (contact capacity AC250 V, 3 A resistance load) or SSR drive output (DC12 V, maximum 20 mA) free switching | |
Input | Thermocouple (K·J·R·T·N·S·B) Resistance thermometer (Pt100 and JPt100) | |
Control Method | ON/OFF, P, PI, PD and PID control | |
Alarm output | Upper limit alarm, lower limit alarm and positive and negative deviation range alarm | |
Sampling period | 100mS | |
Indication accuracy (thermocouple) | Normal temperature: PV±0.3% or ±3℃ (select the larger one) ±1-digit; use it at above 200℃; PV±0.5% or ±2℃ (select the larger one) ±1-digit | |
Indication accuracy (resistance thermometer) | Normal temperature: PV±0.3% or ±3℃ (select the larger one) ±1-digit; use it at above 200℃; PV±0.5% or ±2℃ (select the larger one) ±1-digit | |
Indication accuracy maintenance temperature range | Standard storage: 23±10℃ | |
Power Voltage | AC100~240VAC~50/60Hz±10% |
Input | Thermocouple / Temperature Measuring Resistor | Control Method | ON-OFF Control / PID Control with Self-Tuning / PID Control with Self-Tuning / PI Control / PD Control / P Control / Thermostats | Control Output | Relay Contact Output / SSR Drive Voltage Output |
---|---|---|---|---|---|
Number of Control Points | 1 | Number of Input Points(pcs.) | 1 | Power Supply Voltage | 100::240 |
Failure Detecting Function | Heater Breakage | External Size(mm) | 48×48 |
Please check the type/dimensions/specifications of the part C-MTCTRS in the Temperature Controllers Standard Type series.
How can we improve?
How can we improve?
Thank you for your time.
Your feedback is essential for our continuous improvement
Privacy Policy
Thank you for your cooperation.
Thank you for your time.
Your feedback is essential for our continuous improvement
Please use the inquiry form.
Privacy Policy