  • Due to an increase in demand, the lead time of some of the electrical items from our eCatalogue has increased abnormally and may cause delays in delivery or order suspension. We apologize for the inconvenience and appreciate your kind understanding. Once the supply will get normalized, we will update the same.

Temperature Controller (Outer Diameter 48 × 48 mm / Outer Diameter 96 × 96 mm)

Temperature Controller (Outer Diameter 48 × 48 mm / Outer Diameter 96 × 96 mm)

Click this image to zoom it.

Move the mouse over or click the image to zoom

You can add up to 6 items per a category to the compare list.

Part Number :
    • Starting From :
      9,497₹/Unit
  • Order Qty :
  • Total Price :
    ---
  • Days to ship :
    ---

Select part number to Order Now/ Add to Cart

Product Description

Temperature Regulators - Standard Units
Temperature controllers are devices used to adjust the temperature of the controlled device to the set target temperature
[Feature]
● Dimension (Width X Length X Depth) (mm.)
MTCTR, MTCTRD, MTCTS and MTCTSD - 48 x 48 x 83
MTBGR and MTBGS - 96 x 96 x 86
● Input : Thermocouple (K, J, R, T, N, S, B) and Resistance thermometer (Pt100Ω / JPt100Ω.)
● Output : Relay contact output or SSR drive output
● Power Supply Voltage : AC100 ~ 240V
[Application]
It is used to adjust the temperature of the controlled device to the set target temperature

Temperature Regulators - Standard Units:Related Image

Specifications

Part Number
MTCTR
Part NumberMTCTRMTCTS
O.D. Dimension48×48×83
Control MethodON/OFF control, PID Control with Auto Tuning, PID Control with Selfl-tuning
InputThermocouples (K, J, R, T, N, S, B) Temperature Measuring Resistor (Pt100Ω / JPt100Ω.)
Control Output (OUT1)Relay Contact Output
(Contact Capacity AC250V 3A Resistive Load)
SSR Drive Voltage Output
(DC12V Max. 20mA)
Alarm Output (EV1)Relay Contact Output (Contact Capacity AC250V 2.4A Resistive Load) 1a Contact Point
Control / Alarm Output 2
(OUT2/EV2)
Relay Contact Output (Contact Capacity AC250V 2.4A Resistive Load) 1a Contact Point
Sampling Frequency500mS
Indication Accuracy (Thermocouple)The bigger one of ±0.3% of specified value +1 digit or ±2°C
±3°C for -100 ~ 0°C, ±4°C for -200 ~ -100°C,
no regulation for 400°C or less of B Thermocouple
Indication Accuracy (Temperature Measuring Resistor)The bigger one of ±0.3% of specified value +1 digit or ±2°C
Indication Accuracy Maintenance Temperature RangeAmbient Temperature: 23±10°C
Storage ElementEEPROM
Power Supply VoltageAC100 ~ 240V (Allowable Voltage Change Range 85 ~ 264V)
Power Consumption10VA (max.)
Mass180g or Less

Part Number 

  • Incomplete part number.
    Please use left hand selections to complete a part number.
Loading...
Part Number
MTBGR
MTBGS
MTCTR
MTCTRD
MTCTS
MTCTSD
Part NumberPriceMinimum Order Qty.Volume DiscountDays to ShipRoHSControl Output External Size (A) Heater Breakage Alarm Function

₹ 17,726.80

1 Piece(s) 6 Day(s) or more 10Relay Contact Output96 x 96mmNot Provided

₹ 17,726.80

1 Piece(s) 6 Day(s) or more 10SSR Drive Voltage Output96 x 96mmNot Provided

₹ 9,496.50

1 Piece(s) 6 Day(s) or more 10Relay Contact Output48 x 48mmNot Provided

₹ 18,359.90

1 Piece(s) 6 Day(s) or more 10Relay Contact Output48 x 48mmProvided

₹ 9,496.50

1 Piece(s) 6 Day(s) or more 10SSR Drive Voltage Output48 x 48mmNot Provided

₹ 18,359.90

1 Piece(s) 6 Day(s) or more 10SSR Drive Voltage Output48 x 48mmProvided

Loading...

  1. 1

More Information

Temperature Regulators - Standard Units:Related Image
Temperature Regulators - Standard Units:Related Image
Temperature Regulators - Standard Units:Related Image
Temperature Regulators - Standard Units:Related Image
Be sure to refer to "Precautions on Wire Connection" and "Operating Environment" on >>P.2443.
 

Basic Information

Control Method ON-OFF Control / PID Control with Self-Tuning Number of Control Points 1 Number of Input Points(pcs.) 1
Setting Method Key Input Power Supply Voltage 100::240 Failure Detecting Function Heater Overcurrent